Selective coordination is one of the most misunderstood requirements in commercial electrical design. The intent is straightforward: a fault downstream should clear at the nearest upstream protective device, not at the service entrance. Achieving it in practice requires deliberate analysis and equipment selection.
When a fault occurs in an electrical system, the protective device closest to the fault should operate to clear it, leaving the rest of the system energized. A fault on one branch circuit shouldn’t trip the main breaker or the service entrance breaker.
The failure mode this prevents: a single fault cascading into widespread loss of power because upstream devices tripped along with (or instead of) the device closest to the fault. For emergency and standby systems, this matters even more — the fault that knocks out the emergency lighting and life-safety branch is the fault that should be contained at its source.
The NEC requires selective coordination in specific applications:
"Optional standby" systems (not emergency, not legally required) don’t have a coordination requirement in code — but most facility owners want coordination anyway for operational reliability.
Coordination is achieved by comparing the time-current characteristics (TCC curves) of upstream and downstream devices. For coordination to exist, the downstream device must operate (trip and clear) faster than the upstream device for any possible fault current in the protected zone.
At currents above several thousand amps (typical for faults near the source), most protective devices operate in their instantaneous region. Coordination here depends on careful selection of devices with different instantaneous characteristics. This is often the most challenging part of coordination studies.
At currents in the hundreds to low thousands of amps (typical for faults farther from the source), devices operate on their long-time and short-time delay regions. Adjustable trip units and properly-set delays achieve coordination here.
At currents just above normal load (typical of equipment overload, not faults), thermal overload elements and long-time delays come into play. Coordination at overload is generally easier than at fault conditions.
Modern breakers (Eaton Magnum, Square D MasterPact, ABB Emax, Siemens WL) have electronic trip units with adjustable long-time, short-time, instantaneous, and ground fault settings. Proper setting achieves coordination across a wide fault current range.
Trip units communicate with each other. A downstream device tells the upstream device "I see this fault, you wait." Allows shorter delays on upstream devices than would otherwise be needed for coordination, reducing both arc-flash energy and equipment damage.
Class L, J, or RK fuses with current-limiting characteristics. The let-through current is much less than the available fault current. Allows coordination at high fault levels that breakers alone can’t achieve.
For MV systems and large LV systems, microprocessor protective relays (SEL, Schweitzer, GE Multilin, ABB) provide much finer coordination than breakers alone. Multiple protection elements (overcurrent, ground fault, differential) coordinated against upstream relays.
87-series differential relaying responds only to faults inside the protected zone. Allows fast tripping for internal faults without coordinating against downstream feeder faults.
A proper coordination study produces:
The deliverable typically comes from a qualified electrical engineering firm (not the electrical contractor), using software like SKM PowerTools, ETAP, or EasyPower.
Send us your single-line and protective device list. We will coordinate the study and verify NEC 700/701 compliance.